چکیده:

The dc component of the fault current is the main cause of the current transformer (CT) saturation. The exciting current of the saturated CT depending on the core flux increases and distorts the secondary current, so that the corrupted current waveform may cause the maloperation ofhe protective relays. This paper presents a new, fast, simple -and effective algorithm to compensate the above problem by, adding the calculated exciting current to the measured secondary current and its hardware implementation for this propose.