سال انتشار: ۱۳۸۴

محل انتشار: بیستمین کنفرانس بین المللی برق

تعداد صفحات: ۸

نویسنده(ها):

Mohammad Hejri – Azerbaijan Regional Electric Company Sharif University Of Technology Iran
Hossein Mokhtari – Sharif University Of Technology Iran

چکیده:

Parallel capacitors together with LC-tuned filters are used for reactive power compensation and higher harmonicsuppression in distribution networks. The results of this paper show that the application of parallel capacitors cause current resonance at non-filtered harmonic frequencies. The effects of capacitance division among tuned filters and parallel capacitors on the network frequency characteristic and current resonance
intensity and network voltage distortion are investigated. This paper confirms a design method for eliminating current resonance at non-filtered harmonic frequencies.